Construction:
Copper Conductor , XLPE Insulation, Aluminum/galvanized steel wires Armour, PVC Sheathed
Standards:
BS6346
Application:
These cables are used for electricity supply in low voltage installation system, IEC 60502-1 cables are
suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations,
local energy distributions, industrial plants, where there is no risk of mechanical damage.
Technical Data:
Conductor: Copper conductor, round standed or Shaped,solid round conductor(Class1)or stranded Conductor(Class2) according to IEC60228
Test Voltage: 4000V
Maxium Working Temperature:70 º C
Short-circuit max. Conductor temperature:160°C
Insulation resistance: 20 MΩ x km
Parameter:
No. of Cores | Nominal cross- sectional area | Nominal insulation thickness | Nominal alum wire armor dia. | Nominal sheath thick- ness | Approx. overall diameter | Approx. cable weight |
mm² | mm | mm | mm | mm | kg/mm | |
7 | 1.5 | 0.6 | 0.9 | 1.4 | 15.2 | 500 |
10 | 1.5 | 0.6 | 1.25 | 1.5 | 18.6 | 780 |
12 | 1.5 | 0.6 | 1.25 | 1.5 | 19.4 | 830 |
19 | 1.5 | 0.6 | 1.25 | 1.6 | 22.2 | 1090 |
27 | 1.5 | 0.6 | 1.6 | 1.7 | 26.7 | 1600 |
37 | 1.5 | 0.6 | 1.6 | 1.8 | 29.2 | 1940 |
48 | 1.5 | 0.6 | 1.6 | 1.9 | 32.9 | 2360 |
7 | 2.5 | 0.7 | 1.25 | 1.5 | 18 | 750 |
10 | 2.5 | 0.7 | 1.25 | 1.6 | 21.8 | 1000 |
12 | 2.5 | 0.7 | 1.25 | 1.6 | 22.4 | 1080 |
19 | 2.5 | 0.7 | 1.6 | 1.7 | 26.6 | 1640 |
27 | 2.5 | 0.7 | 1.6 | 1.8 | 30.7 | 2110 |
37 | 2.5 | 0.7 | 1.6 | 1.9 | 34 | 2600 |
48 | 2.5 | 0.7 | 2 | 2.1 | 39.5 | 3520 |
7 | 4 | 0.8 | 1.25 | 1.6 | 20.5 | 970 |
10 | 4 | 0.8 | 1.6 | 1.7 | 26.1 | 1500 |
12 | 4 | 0.8 | 1.6 | 1.7 | 26.8 | 1630 |
19 | 4 | 0.8 | 1.6 | 1.8 | 30.5 | 2170 |
27 | 4 | 0.8 | 2 | 2 | 37.1 | 3170 |
37 | 4 | 0.8 | 2 | 2.1 | 40.8 | 3910 |
48 | 4 | 0.8 | 2 | 2.2 | 46 | 4790 |